K25 — California Building Standards Code
K25 carries the highest importance rating in the entire California Supplemental Examination (CSE) blueprint. Keep its rules straight by anchoring what each rule protects first, and the number snaps right onto it.
A. California Building Standards Code
People casually say "Title 24" when they mean energy calcs, and the exam happily punishes that shortcut. Title 24 is the entire California Building Standards Code, and the Energy Code is just Part 6.
- The California Building Standards Commission (BSC) publishes a new edition every three years. The edition in effect when the permit application is submitted governs, plus any stricter local amendments.
- This course teaches the 2025 edition, in effect since January 1, 2026, linked on the California Architects Board (CAB) reference list.
- Wildfire construction rules now live in the Wildland-Urban Interface Code (Part 7), with California Building Code (CBC) Chapter 7A and Fire Code Chapter 49 pointing there. CAB's list names both Part 7 and the Fire Code (Part 9), covered in K35.
| Part | Subject | Part | Subject |
|---|---|---|---|
| 2 | Building | 7 | Wildland-Urban Interface |
| 5 | Plumbing | 9 | Fire |
| 6 | Energy | 11 | Green Building Standards (CALGreen) |
Memorize these six parts by number. Each part applies on its own (meeting CALGreen never waives Part 6 Energy compliance).
B. California Building Code
The CBC (Part 2) is the International Building Code (IBC) with California amendments, enforced locally by the building department.
| CBC chapter | What it covers |
|---|---|
| 3 | Occupancy classification |
| 5 | Building heights and areas |
| 6 | Types of construction |
| 7 | Fire and smoke protection features |
| 8 | Interior finishes |
| 9 | Fire protection and life safety systems |
| 10 | Means of egress |
| 11A / 11B | Housing accessibility / public accommodation and commercial accessibility |
| 14 | Exterior walls |
| 16 / 17 | Structural design / special inspections and tests |
Occupancy, construction type and risk category
Keep three separate drawers: occupancy is how the building is used, construction type is what it's built of and how fire-resistant it is, and risk category is how bad a structural failure would be.
1. Occupancy groups
| Group | Use | Examples |
|---|---|---|
| A Assembly | Generally 50 or more people gathering | A-1 theaters, A-2 restaurants and nightclubs, A-3 worship, libraries, and museums, A-4 indoor arenas, A-5 outdoor stadiums |
| B Business | Offices and services | Offices, banks, doctors' offices |
| E Educational | Through 12th grade | Schools with more than 6 students |
| F Factory | Manufacturing | F-1 moderate hazard, F-2 low hazard |
| H High hazard | Dangerous materials | H-1 through H-5 |
| I Institutional | People cared for or supervised | Hospitals and jails |
| M Mercantile | Selling goods | Stores and markets |
| R Residential | Sleeping | R-1 hotels, R-2 apartments and dorms, R-3 other housing, R-4 residential care |
| S Storage | Non-hazardous storage | Warehouses, parking garages |
| U Utility | Accessory buildings | Barns, carports, sheds |
Watch that 50-person line: a café or meeting room with fewer than 50 occupants is generally Group B, not assembly.
2. Construction types
- Types I and II are generally noncombustible. Type I-A has a 3-hour primary structural frame (2 hours for I-B).
- Type III pairs noncombustible exterior walls with combustible interiors, Type IV is heavy timber, and Type V allows ordinary wood framing.
- An A suffix (like V-A) means protected with rated elements. A B suffix means unprotected.
3. Risk categories
Risk Categories I to IV rank failure consequences: most buildings are Category II, while essential facilities like hospitals and fire stations are Category IV.
Putting them together
- Run every code analysis in order: occupancy → construction type → siting on the lot → allowable area → height and stories.
- Occupancy, construction type, and sprinklers set allowable height, stories, and floor area. Change the use inside the exact same footprint, and the code analysis starts over.
- Any building with an occupied floor more than 75 feet above the lowest fire department vehicle access is a high-rise.
Turn a Group B office into a 120-seat restaurant (Group A-2) with the same footprint, and everything resets: exits, exit width, and plumbing fixtures change, an A-2 fire area with 100 or more occupants needs sprinklers, and mixed uses may need a rated separation.
C. Fire and life safety
Passive protection
Passive fire protection uses rated construction to hold back fire and smoke. The whole assembly counts, including openings, roof-deck joints, and penetrations. One unsealed duct penetration or deeper recessed fire extinguisher cabinet can defeat a rated wall.
- A fire wall runs continuously from the foundation to or through the roof and stays standing if one side collapses, legally splitting one structure into separate buildings.
- Fire barriers separate exit enclosures, occupancies, and fire areas. Fire partitions sit a tier below (like 1-hour corridor walls), and smoke barriers resist smoke movement.
- Hourly fire-resistance ratings come from ASTM E119 or UL 263, never from a finish's ASTM E84 flame spread test.
- Interior finishes are classed by flame spread: Class A is the best, then B, then C (exits and corridors generally need the better classes).
- Doors and windows in rated walls are opening protectives and may carry a lower rating than the wall (a 2-hour fire barrier typically takes a 1½-hour door).
- Exterior walls are rated by fire separation distance to the lot line, street center, or an imaginary line between buildings: closer means a higher rating and fewer openings.
Active systems and egress
Active fire protection fights or announces fire with equipment: sprinklers, standpipes (hose connections), the fire department connection, detection and alarms, smoke control, and emergency lighting and exit signs.
- Every means of egress has three parts: exit access → exit → exit discharge, ending at the public way.
- Occupant load uses the code table's floor area per occupant. Required width = occupants × 0.3 inch for stairs, 0.2 inch for other components (minimum widths still apply).
- Exits per story: 2 for up to 500 people, 3 for 501 to 1,000, and 4 for more than 1,000. A small occupant count never allows a single exit without a specific code exception.
- Separate two required exits by at least half the overall diagonal, or a third with sprinklers.
- Stairs: 44 inches minimum width (36 inches under 50 people).
- Ramps: 1:12 maximum slope.
- Exit stair enclosures: 1-hour for fewer than four stories, 2-hour for four or more.
- Corridors: 44 inches minimum (36 under 50 people), often rated. Doors serving 50 or more people swing in the direction of travel.
- An exit can't pass through a locked stockroom or another tenant's space (even with the neighbor's written blessing). Accessible routes live in K30.
Egress calculations
Take a 1,200-net-square-foot room with a factor of 15 net square feet per person: 1,200 ÷ 15 = 80 occupants (use net or gross area exactly as listed and round fractions up).
Check exit count, separation, capacity, and minimum sizes separately. Capacity asks for 80 × 0.3 inch = 24 inches of stair, yet the 44-inch minimum governs. Across a 120-foot unsprinklered diagonal, two exits must sit at least 60 feet apart.
D. Structural provisions
- Dead load is permanent building weight (structure, finishes, fixed equipment). Live load comes from use. Wind, snow, rain, and earthquake loads are separate.
- Sideways force is resisted by shear walls, moment frames (rigid joints), or braced frames (diagonals).
- Loads need an unbroken path: diaphragm → collectors and connections → frame or wall → foundation → soil. Strong parts can't save a missing link.
- Essential facilities are Risk Category IV. Keep that distinct from K24's "essential services buildings": an emergency power station is an essential facility (Category IV), not an essential services building.
E. Nonstructural elements
Nonstructural components (ceilings, cladding, equipment, piping) can fall or tip while the frame barely scratches. Brace or anchor them back to the structure.
- Vibration isolators never replace seismic restraints. Equipment still needs restraint against sliding and tipping, with flexible connections where parts move differently.
- Ceiling-grid light fixtures need independent supports and safety wires.
F. California Residential Code
The Residential Code (Part 2.5) covers detached one- and two-family homes and townhouses up to three stories above grade plane.
Question
The occupant load factor for this use is gross. Can the team subtract the corridors and restrooms first, like it's net?
G. Other Title 24 parts
- The Historical Building Code (Part 8) offers alternatives for qualified historic buildings, though merely being old isn't enough: the building must sit on a historic register or inventory. New additions follow regular code, and the Energy Code still applies to new lighting.
- The Existing Building Code (Part 10) covers repairs, alterations, additions, and occupancy changes in existing buildings.
- The Fire Code (Part 9) covers fire hazards, operations, and emergency access.
H. California and model codes
- California adopts model codes and amends them (IBC, National Electrical Code, Uniform Mechanical and Plumbing Codes), meaning unamended model text isn't always the California rule.
- California amendments appear in italics with the adopting agency in brackets: [BSC] for Building Standards Commission, [SFM] for State Fire Marshal, [DSA] for Division of the State Architect, and [OSHPD] for hospitals (Office of Statewide Health Planning and Development, now the Department of Health Care Access and Information).
- California goes farthest past model codes on seismic design, special inspections, wildfire construction, split accessibility chapters (11A and 11B), energy, and green building.
K25 / Quick check
Quiz
TLDR · Quick Reference
- Title 24
- The entire California Building Standards Code, not just energy. Part 2 Building, Part 5 Plumbing, Part 6 Energy, Part 7 Wildland-Urban Interface, Part 9 Fire, and Part 11 Green Building Standards (CALGreen).
- Edition
- Updated every three years (2025 edition, effective January 1, 2026). The edition in effect when the permit application is submitted governs, plus local amendments.
- Occupancy / type / risk
- What it's used for, what it's built of, and how badly a failure hurts. Three separate classifications.
- Passive vs. active fire protection
- Rated assemblies hold back fire and smoke (openings and penetrations included). Sprinklers and alarms detect or fight it.
- Egress
- Exit access → exit → exit discharge → public way.
- Egress numbers
- 0.3 inch/occupant for stairs, 0.2 for other parts. Stairs 44 inches min (36 under 50 people). Exits: 2 up to 500 people, 3 for 501 to 1,000, 4 above 1,000.
- Structure
- Dead load is permanent weight, live load comes from use, and every load needs an unbroken path to soil.
- Fire wall
- Runs continuously from foundation to or through the roof and stays standing if one side collapses. Type I-A primary frame is 3-hour (I-B is 2-hour).
Student Q&A
Questions students asked about K25, with answers from The Exit Club. All questions
Loading questions…
Something in K25 unclear? Log in to ask a question.
Log in to askYour questions
Sources & handbook wording
K25 · Knowledge of methods and procedures for complying with California Building Standards Code related to design and construction.
- CAB CSE Handbook, April 2026 ↗
PDF p.13, K25. Official scope only
- 2025 California Building Code: Occupancy ↗
Chapter 3. CAB-listed chapter
- 2025 California Building Code: Heights and Areas ↗
Chapter 5. CAB-listed chapter
- 2025 California Building Code: Fire and Smoke Protection ↗
Chapter 7. CAB-listed chapter
- 2025 California Building Code: Egress ↗
Chapter 10. Egress capacity, components and exceptions
- 2025 California Building Code: Structural Design ↗
Chapter 16. Design loads and risk