K25 — California Building Standards Code

K25 carries the highest importance rating in the entire California Supplemental Examination (CSE) blueprint. Keep its rules straight by anchoring what each rule protects first, and the number snaps right onto it.

A. California Building Standards Code

People casually say "Title 24" when they mean energy calcs, and the exam happily punishes that shortcut. Title 24 is the entire California Building Standards Code, and the Energy Code is just Part 6.

Title 24 is the whole code. The CBC is one part of it.A large oval is Title 24, the California Building Standards Code, adopted by the Building Standards Commission. Inside it are Part 2, the Building Code (CBC), Part 6, the Energy Code, and Part 11, CALGreen, plus ten more parts. Outside the oval, the International Building Code, a national model code, feeds into Part 2 with a dashed arrow, because California adopts and amends it. Calling energy calcs “Title 24” is shop talk. On the exam, Title 24 means the whole code.Title 24 is the whole code. The CBC is one part of it.InternationalBuilding Code(IBC)A national modelcode, not law hereTitle 24: California Building Standards CodeAdopted by the Building Standards CommissionPart 2Building Code(CBC)Part 6Energy CodePart 11CALGreen+ 10 more partsadopted andamendedOn the exam, Title 24 means the whole code, not just energy calcs.Title 24 is the whole code. The CBC is one part of it.A large oval is Title 24, the California Building Standards Code, adopted by the Building Standards Commission. Inside it are Part 2, the Building Code (CBC), Part 6, the Energy Code, and Part 11, CALGreen, plus ten more parts. Outside the oval, the International Building Code, a national model code, feeds into Part 2 with a dashed arrow, because California adopts and amends it. Calling energy calcs “Title 24” is shop talk. On the exam, Title 24 means the whole code.Title 24 is the whole code.The CBC is one part of it.InternationalBuilding Code(IBC)adopted, amendedTitle 24California BuildingStandards CodePart 2Building Code(CBC)Part 6EnergyPart 11CALGreen+ 10 moreOn the exam, Title 24 means thewhole code, not just energy calcs.
  • The California Building Standards Commission (BSC) publishes a new edition every three years. The edition in effect when the permit application is submitted governs, plus any stricter local amendments.
  • This course teaches the 2025 edition, in effect since January 1, 2026, linked on the California Architects Board (CAB) reference list.
  • Wildfire construction rules now live in the Wildland-Urban Interface Code (Part 7), with California Building Code (CBC) Chapter 7A and Fire Code Chapter 49 pointing there. CAB's list names both Part 7 and the Fire Code (Part 9), covered in K35.
Part Subject Part Subject
2 Building 7 Wildland-Urban Interface
5 Plumbing 9 Fire
6 Energy 11 Green Building Standards (CALGreen)

Memorize these six parts by number. Each part applies on its own (meeting CALGreen never waives Part 6 Energy compliance).

B. California Building Code

The CBC (Part 2) is the International Building Code (IBC) with California amendments, enforced locally by the building department.

CBC chapter What it covers
3 Occupancy classification
5 Building heights and areas
6 Types of construction
7 Fire and smoke protection features
8 Interior finishes
9 Fire protection and life safety systems
10 Means of egress
11A / 11B Housing accessibility / public accommodation and commercial accessibility
14 Exterior walls
16 / 17 Structural design / special inspections and tests

Occupancy, construction type and risk category

Keep three separate drawers: occupancy is how the building is used, construction type is what it's built of and how fire-resistant it is, and risk category is how bad a structural failure would be.

Three separate classificationsThree boxes. 1, occupancy: what the building is used for, groups A, B, E through U, set in CBC Chapter 3. It drives area limits, exits, separations and more. 2, construction type: what the building is built of and how fire-resistant it is, Types I to V, set in CBC Chapter 6. Types I and II are noncombustible and Type V is combustible. 3, risk category: how bad a failure would be, Categories I to IV, set in CBC Chapter 16. It sets structural loads, and Category IV is essential facilities. A 120-seat restaurant can be Group A-2, Type V-B and Risk Category II all at once.Three separate classifications1OccupancyWhat is itused for?A, B, E … USets area limits, exits,separations and moreCBC Chapter 32Construction typeWhat is it built of, andhow fire-resistant is it?Types I to VI and II noncombustible,V combustibleCBC Chapter 63Risk categoryHow bad would afailure be?I to IVSets structural loads.IV = essential facilitiesCBC Chapter 16A 120-seat restaurant can be Group A-2, Type V-B and Risk Category II, all at once.Three separate classificationsThree boxes. 1, occupancy: what the building is used for, groups A, B, E through U, set in CBC Chapter 3. It drives area limits, exits, separations and more. 2, construction type: what the building is built of and how fire-resistant it is, Types I to V, set in CBC Chapter 6. Types I and II are noncombustible and Type V is combustible. 3, risk category: how bad a failure would be, Categories I to IV, set in CBC Chapter 16. It sets structural loads, and Category IV is essential facilities. A 120-seat restaurant can be Group A-2, Type V-B and Risk Category II all at once.Three separateclassifications1OccupancyWhat is itused for?A, B, E … USets area limits, exits,separations and moreCBC Chapter 32Construction typeWhat is it built of, andhow fire-resistant is it?Types I to VI and II noncombustible,V combustibleCBC Chapter 63Risk categoryHow bad would afailure be?I to IVSets structural loads.IV = essential facilitiesCBC Chapter 16A 120-seat restaurant can be GroupA-2, Type V-B and Risk Category II,all at once.

1. Occupancy groups

Group Use Examples
A Assembly Generally 50 or more people gathering A-1 theaters, A-2 restaurants and nightclubs, A-3 worship, libraries, and museums, A-4 indoor arenas, A-5 outdoor stadiums
B Business Offices and services Offices, banks, doctors' offices
E Educational Through 12th grade Schools with more than 6 students
F Factory Manufacturing F-1 moderate hazard, F-2 low hazard
H High hazard Dangerous materials H-1 through H-5
I Institutional People cared for or supervised Hospitals and jails
M Mercantile Selling goods Stores and markets
R Residential Sleeping R-1 hotels, R-2 apartments and dorms, R-3 other housing, R-4 residential care
S Storage Non-hazardous storage Warehouses, parking garages
U Utility Accessory buildings Barns, carports, sheds

Watch that 50-person line: a café or meeting room with fewer than 50 occupants is generally Group B, not assembly.

2. Construction types

  • Types I and II are generally noncombustible. Type I-A has a 3-hour primary structural frame (2 hours for I-B).
  • Type III pairs noncombustible exterior walls with combustible interiors, Type IV is heavy timber, and Type V allows ordinary wood framing.
  • An A suffix (like V-A) means protected with rated elements. A B suffix means unprotected.

3. Risk categories

Risk Categories I to IV rank failure consequences: most buildings are Category II, while essential facilities like hospitals and fire stations are Category IV.

Putting them together

  • Run every code analysis in order: occupancy → construction type → siting on the lot → allowable area → height and stories.
  • Occupancy, construction type, and sprinklers set allowable height, stories, and floor area. Change the use inside the exact same footprint, and the code analysis starts over.
  • Any building with an occupied floor more than 75 feet above the lowest fire department vehicle access is a high-rise.

Turn a Group B office into a 120-seat restaurant (Group A-2) with the same footprint, and everything resets: exits, exit width, and plumbing fixtures change, an A-2 fire area with 100 or more occupants needs sprinklers, and mixed uses may need a rated separation.

C. Fire and life safety

Passive protection

Passive fire protection uses rated construction to hold back fire and smoke. The whole assembly counts, including openings, roof-deck joints, and penetrations. One unsealed duct penetration or deeper recessed fire extinguisher cabinet can defeat a rated wall.

  • A fire wall runs continuously from the foundation to or through the roof and stays standing if one side collapses, legally splitting one structure into separate buildings.
  • Fire barriers separate exit enclosures, occupancies, and fire areas. Fire partitions sit a tier below (like 1-hour corridor walls), and smoke barriers resist smoke movement.
  • Hourly fire-resistance ratings come from ASTM E119 or UL 263, never from a finish's ASTM E84 flame spread test.
  • Interior finishes are classed by flame spread: Class A is the best, then B, then C (exits and corridors generally need the better classes).
  • Doors and windows in rated walls are opening protectives and may carry a lower rating than the wall (a 2-hour fire barrier typically takes a 1½-hour door).
  • Exterior walls are rated by fire separation distance to the lot line, street center, or an imaginary line between buildings: closer means a higher rating and fewer openings.

Active systems and egress

Active fire protection fights or announces fire with equipment: sprinklers, standpipes (hose connections), the fire department connection, detection and alarms, smoke control, and emergency lighting and exit signs.

Three parts of egress, ending at the public wayThe means of egress has three parts in order, and it ends at the public way. Exit access is the room, corridor and path leading to an exit. The exit is a protected component such as a stair enclosure or exterior exit door. Exit discharge runs from the exit to the outside and away from the building. The public way, the destination, is a street, alley or other open space. Travel distance and dead ends are measured in exit access, and the route is not complete until people reach the public way.Three parts of egress, ending at the public way1Exit accessRooms and corridorsleading to an exit2ExitA protected stair oran exit door3Exit dischargeFrom the exit out toopen airDestinationPublic wayA street, alley oropen spaceTravel distance and dead ends are measured in exit access.The route isn’t done until people reach the public way.An enclosed courtyard with no way out isn’t the end of the route.Three parts of egress, ending at the public wayThe means of egress has three parts in order, and it ends at the public way. Exit access is the room, corridor and path leading to an exit. The exit is a protected component such as a stair enclosure or exterior exit door. Exit discharge runs from the exit to the outside and away from the building. The public way, the destination, is a street, alley or other open space. Travel distance and dead ends are measured in exit access, and the route is not complete until people reach the public way.Three parts of egress,ending at the public way1Exit accessRooms and corridors leading to an exit2ExitA protected stair or an exit door3Exit dischargeFrom the exit out to open airEndPublic wayA street, alley or open spaceTravel distance and dead ends aremeasured in exit access.The route isn’t done until peoplereach the public way.
  • Every means of egress has three parts: exit access → exit → exit discharge, ending at the public way.
  • Occupant load uses the code table's floor area per occupant. Required width = occupants × 0.3 inch for stairs, 0.2 inch for other components (minimum widths still apply).
  • Exits per story: 2 for up to 500 people, 3 for 501 to 1,000, and 4 for more than 1,000. A small occupant count never allows a single exit without a specific code exception.
  • Separate two required exits by at least half the overall diagonal, or a third with sprinklers.
  • Stairs: 44 inches minimum width (36 inches under 50 people).
  • Ramps: 1:12 maximum slope.
  • Exit stair enclosures: 1-hour for fewer than four stories, 2-hour for four or more.
  • Corridors: 44 inches minimum (36 under 50 people), often rated. Doors serving 50 or more people swing in the direction of travel.
  • An exit can't pass through a locked stockroom or another tenant's space (even with the neighbor's written blessing). Accessible routes live in K30.

Egress calculations

Take a 1,200-net-square-foot room with a factor of 15 net square feet per person: 1,200 ÷ 15 = 80 occupants (use net or gross area exactly as listed and round fractions up).

Check exit count, separation, capacity, and minimum sizes separately. Capacity asks for 80 × 0.3 inch = 24 inches of stair, yet the 44-inch minimum governs. Across a 120-foot unsprinklered diagonal, two exits must sit at least 60 feet apart.

D. Structural provisions

  • Dead load is permanent building weight (structure, finishes, fixed equipment). Live load comes from use. Wind, snow, rain, and earthquake loads are separate.
  • Sideways force is resisted by shear walls, moment frames (rigid joints), or braced frames (diagonals).
  • Loads need an unbroken path: diaphragm → collectors and connections → frame or wall → foundation → soil. Strong parts can't save a missing link.
  • Essential facilities are Risk Category IV. Keep that distinct from K24's "essential services buildings": an emergency power station is an essential facility (Category IV), not an essential services building.

E. Nonstructural elements

Nonstructural components (ceilings, cladding, equipment, piping) can fall or tip while the frame barely scratches. Brace or anchor them back to the structure.

  • Vibration isolators never replace seismic restraints. Equipment still needs restraint against sliding and tipping, with flexible connections where parts move differently.
  • Ceiling-grid light fixtures need independent supports and safety wires.

F. California Residential Code

The Residential Code (Part 2.5) covers detached one- and two-family homes and townhouses up to three stories above grade plane.

Question

The occupant load factor for this use is gross. Can the team subtract the corridors and restrooms first, like it's net?

G. Other Title 24 parts

  • The Historical Building Code (Part 8) offers alternatives for qualified historic buildings, though merely being old isn't enough: the building must sit on a historic register or inventory. New additions follow regular code, and the Energy Code still applies to new lighting.
  • The Existing Building Code (Part 10) covers repairs, alterations, additions, and occupancy changes in existing buildings.
  • The Fire Code (Part 9) covers fire hazards, operations, and emergency access.

H. California and model codes

  • California adopts model codes and amends them (IBC, National Electrical Code, Uniform Mechanical and Plumbing Codes), meaning unamended model text isn't always the California rule.
  • California amendments appear in italics with the adopting agency in brackets: [BSC] for Building Standards Commission, [SFM] for State Fire Marshal, [DSA] for Division of the State Architect, and [OSHPD] for hospitals (Office of Statewide Health Planning and Development, now the Department of Health Care Access and Information).
  • California goes farthest past model codes on seismic design, special inspections, wildfire construction, split accessibility chapters (11A and 11B), energy, and green building.

K25 / Quick check

Quiz

16 questions
← Quiz list
Question 1 of 16Choose one answer
An architect is coordinating a new three-story office building with the plumbing engineer and the fire protection engineer. The consultants ask which parts of Title 24 contain the California Plumbing Code and the California Fire Code. The architect should refer them to which of the following?

TLDR  ·  Quick Reference

Title 24
The entire California Building Standards Code, not just energy. Part 2 Building, Part 5 Plumbing, Part 6 Energy, Part 7 Wildland-Urban Interface, Part 9 Fire, and Part 11 Green Building Standards (CALGreen).
Edition
Updated every three years (2025 edition, effective January 1, 2026). The edition in effect when the permit application is submitted governs, plus local amendments.
Occupancy / type / risk
What it's used for, what it's built of, and how badly a failure hurts. Three separate classifications.
Passive vs. active fire protection
Rated assemblies hold back fire and smoke (openings and penetrations included). Sprinklers and alarms detect or fight it.
Egress
Exit access → exit → exit discharge → public way.
Egress numbers
0.3 inch/occupant for stairs, 0.2 for other parts. Stairs 44 inches min (36 under 50 people). Exits: 2 up to 500 people, 3 for 501 to 1,000, 4 above 1,000.
Structure
Dead load is permanent weight, live load comes from use, and every load needs an unbroken path to soil.
Fire wall
Runs continuously from foundation to or through the roof and stays standing if one side collapses. Type I-A primary frame is 3-hour (I-B is 2-hour).

Student Q&A

Questions students asked about K25, with answers from The Exit Club. All questions

Loading questions…

Sources & handbook wording

K25 · Knowledge of methods and procedures for complying with California Building Standards Code related to design and construction.

  1. CAB CSE Handbook, April 2026 ↗

    PDF p.13, K25. Official scope only

  2. 2025 California Building Code: Occupancy ↗

    Chapter 3. CAB-listed chapter

  3. 2025 California Building Code: Heights and Areas ↗

    Chapter 5. CAB-listed chapter

  4. 2025 California Building Code: Fire and Smoke Protection ↗

    Chapter 7. CAB-listed chapter

  5. 2025 California Building Code: Egress ↗

    Chapter 10. Egress capacity, components and exceptions

  6. 2025 California Building Code: Structural Design ↗

    Chapter 16. Design loads and risk